When a Transmitter is configured to use an MQTT Transmission History Store, data is written to the History Store once MQTT Transmission has determined that there is a connection failure which can be up to 1.5 times the configured keep alive. As such any data published during this time can be lost.
In order to cover data loss during a keep alive timeout scenario, the MQTT Transmission History Store includes a Rolling History Buffer that can be configured in the Advanced Properties configuration section. When the Rolling History Buffer is enabled, all tag changes will be written to the History Store regardless of connection status.
It can take MQTT Transmission 1.5 times the configured Server Keep Alive time to determined that there is a connection failure. The Rolling History Max Age should be at least 2x the Transmitter Server Keep Alive timeout to ensure that all tag change events are captured during this period.