The history configuration for MQTT Engine tags can be configured as needed for your specific requirements as described in Ignition's Configuring Tag History and How the Tag Historian System Works documents.
However, when using MQTT Store and Forward where historical events will be published, there are some caveats to be aware of.
MQTT Engine has two ways to process historical events and insert the historical data into Ignition's Tag Historian module
The configuration parameters required to write historical events directly to the database, via the Historian, bypassing the Tag are shown below.
Under the MQTT Engine Settings General Tab, navigate to the Miscellaneous Settings and ensure Store Historical events is selected
History must be enabled on the tag but the only property used from the tag history configuration is the Storage Provider.
All historic data will be written to Storage Provider, via the Historian, using the timestamp associated with the historical data.
There are several reasons why you might need to write directly to the tag which include:
The configuration parameters required to write historical events to the Tag instead of directly to the Historian are detailed below.
Under the MQTT Engine Settings General Tab, navigate to the Miscellaneous Settings and ensure Store Historical events is de-selected
History must be enabled on the tag but the two settings required are:
All historic data will be written to Storage Provider, via the Historian, using the timestamp associated with the historical data.
When configuring MQTT Engine to write historical events directly to the tag, the Edge side client must publish historic data in-order (synchronously) before live data resumes.
This is because because Ignition will ignore writes to the tag if the timestamp on the tag change is older that the current value.
If you are using MQTT Transmission, under the MQTT Transmission Settings for your transmitter, navigate to the History Settings and ensure that In-Order History is selected.
This ensures that when the Edge side client comes back online and flushes history, it will flush the oldest historical events first (in order) before sending live Tag changes events to Engine.