As en example, let's configure the driver to poll for Event records and disable polling for Alarms and History. This can be done in two ways:
...
- Alarm Scan Rate
- Set to -1 to disable polling for Alarms. If Alarms are not needed, it is the best practice to set the 'Alarm Scan Rate' to -1. With this setup, alarm records are not going to be pushed to the rs_efm_meter_alarm database table regardless of the alarm source setting (i.e. PERIODIC_HISTORY or ALARM_LOG_RECORDS).
- If the 'Alarm Source' is set to the 'ALARM_LOG_RECORDS' and the 'Record Info Scan Rate' is set to -1, the 'Alarm Scan Rate' can be set to 0. With this setup, the AlarmPoller will not run on it own nor will it poll on notifications from the RecordInfoPoller.
- Event Scan rate
- Set to a positive number to launch the EventPoller with specified poll rate.
- Periodic History Scan Rate
- Set to -1 to disable polling for Periodic History records.
- If the 'Record Info Scan Rate' is set to -1, the 'Periodic History Scan Rate' can be set to 0. With this setup, the PeriodicHistoryPoller will not run on it own nor will it poll on notifications from the RecordInfoPoller.
- Daily History Scan Rate
- Set to -1 to disable polling for Daily History records.
- If the 'Record Info Scan Rate' is set to -1, the 'Daily History Scan Rate' can be set to 0. With this setup, the DailyHistoryPoller will not run on it own nor will it poll on notifications from the RecordInfoPoller.
- Record Info Scan Rate
- Set to -1 to disable the RecordInfoPoller so that there will be no notifications to Alarm, Events and History pollers on any 'RecordInfo' change such as 'Last Record Sequence number Used', etc.
...
- Alarm Scan Rate
- Set to -1 to disable polling for Alarms.
- Event Scan rate
- 0 Scan on notification form the 'Record Info' poller.
- Periodic History Scan Rate
- Set to -1 to disable polling for Periodic History records.
- Daily History Scan Rate
- Set to -1 to disable polling for Daily History records.
- Record Info Scan Rate
- Set to a positive number to launch the RecordInfoPoller with specified poll rate. With this setup, EventPoller will be notified on any 'RecordInfo' change such as 'Last Record Sequence number Used', etc.
![](/download/attachments/69730621/EFM%20ABB%20Totalflow%20Poll%20Events%20on%20Notifications.png?version=1&modificationDate=1596844171000&api=v2)
At this point, the EFM ABB Totalflow driver is configured and is polling for Events at the rate specified in the EFM ABB Totalflow device configuration.
...