When Max Time Between Samples is greater than 0, it is not honored during historical data flushes because the tag updates for historical data occur too quickly. See example for this configuration. |
If you are not using reference tags, the Edge side client must publish historic data in-order (synchronously) before live data resumes. This is because Ignition will ignore writes to the tag if the timestamp on the tag change is older that the current value.
...