- Alarm Scan Rate
- Set to -1 to disable polling for Alarms. If Alarms are not needed it is the best to set the 'Alarm Scan Rate' to -1. With this setup, alarm records are not going to be pushed to the rs_efm_meter_alarm database table regardless of the alarm source setting (i.e. PERIODIC_HISTORY or ALARM_LOG_RECORDS).
- If the 'Alarm Source' is set to the 'ALARM_LOG_RECORDS' and the 'Record Info Scan Rate' is set to -1, the 'Alarm Scan Rate' can be set to 0. With this setup, the AlarmPoller will not run on it own nor will it poll on notification from the RecordInfoPoller.
- Event Scan Rate
- Set to -1 to disable polling for Events.
- If the 'Record Info Scan Rate' is set to -1, the 'Event Scan Rate' can be set to 0. With this setup, the EventPoller will not run on it own or on notification from the RecordInfoPoller.
- Periodic History Scan Rate
- Set to a positive number to launch the PeriodicHistoryPoller with specified poll rate.
- Daily History Scan Rate
- Set to a positive number to launch the DailyHistoryPoller with specified poll rate.
- Record Info Scan Rate
- Set to -1 to disable the RecordInfoPoller so that there will be no notifications to Alarm, Events and History pollers on any 'RecordInfo' change such as 'Last Record Sequence number Used', etc.
...