- Configure a History Store with a large storage time for your tags.
- Disconnect the Edge for a set time period to cause MQTT Transmission to store data to the History Store using one of the methods detailed below:
- Disable the network connection
- Disable the broker
- Use Primary Host ID in both MQTT Engine and in the MQTT Transmission.
- Removing the Primary Host ID from MQTT Engine will simulate the primary backend application going offline and cause MQTT Transmission to store data to the History Store.
- Restoring the Primary Host ID to MQTT Engine will simulate that the primary backend application is online and cause MQTT Transmission to flush the stored data
- Modify the MQTT Transmission client credentials at the broker preventing the client from connecting
...