For help using PAC Control, see the PAC Control Userís User's Guide (available from the Opto 22 website).
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
For each tag to be scanned, create a string element following the OptoScript Syntax and tag naming standard.
IMPORTANT: Index number 0 (zero) must be the last item initialized in the OptoScript block
...
Code Block | ||
---|---|---|
| ||
/* |
...
If the tag begins with an ' or a /, the tag is ignored. |
...
Important! Initialize the first table element (at Index 0) last (because |
...
a blank string in Index 0 tells the driver that the |
...
string table has not yet been initialized). |
...
*/ |
...
stPublicListOfStrategyTags[0] = ""; |
...
stPublicListOfStrategyTags[1] = "f32.MyFloat.rw"; |
...
stPublicListOfStrategyTags[2] = "i64.MyInt64.rw"; |
...
stPublicListOfStrategyTags[3] = "s.MyString.rw"; |
...
stPublicListOfStrategyTags[4] = "t.MyTimer.rw"; |
...
stPublicListOfStrategyTags[5] = "i32b.MyBool.rw"; |
...
stPublicListOfStrategyTags[6] = "i32t.MyInt32Table[0-9].rw"; |
...
stPublicListOfStrategyTags[7] = "i64t. MyInt64Table [0-20].rw"; |
...
stPublicListOfStrategyTags[8] = "f32t.MyFloatTable[10-19].rw"; |
...
stPublicListOfStrategyTags[9] = "st. MyStringTable [0-9].rw"; |
...
stPublicListOfStrategyTags[10] = "dio.MyDiscreetPoint"; |
...
stPublicListOfStrategyTags[11] = "aio. MyAnalogPoint.rw"; |
...
stPublicListOfStrategyTags[12] = "i32te.MyInt32TableElement[5].rw"; |
...
stPublicListOfStrategyTags[13] = "i32tebp.MyInt32TableElementBitPick [9].2.rw"; |
...
stPublicListOfStrategyTags[14] = "i64tebp. MyInt64TableElementBitPick [5].8.rw"; |
...
stPublicListOfStrategyTags[16] = "i32bp.MyInt32BitPick.1.rw"; |
...
// Remember, initialize index 0 last! |
...
stPublicListOfStrategyTags[0] = "i32.Int32.rw"; |
In the OptoScript block, you:*
...
stPublicListOfStrategyTags[<index number>] = "<modified tag name>";
...
Code Block | ||
---|---|---|
| ||
stPublicListOfStrategyTags[1] = "s.MyStringVariable"; |
To construct the tag name, see Naming Standard.*
...
...
In the OptoScript block, you reference PAC Control tags using a pre-defined naming standard that consists of the tagís:*
...
...
...
...
Notes*
...
...
...
Code Block | ||
---|---|---|
| ||
/i32.MyIntVariable.rw |
...
's.MyStringVariable |
Naming standard: <OptoScript data type code>.<PAC Control tag name>[<index number or range>].<bit location>.< writeable attribute>
Examples:
Data type description | Ignition data type | Data type code | Example tag name for OptoScript block | Example tag name for OptoScript block (writeable tag) | Notes | Ignition will display tag name as: |
---|---|---|---|---|---|---|
32-bit integer | Int4 | i32 | i32.MyIntVariable |
| MyIntVariable__i32 | |
64-bit integer | Int8 | i64 | i64.MyLongVariable |
| MyLongVariable__i64 | |
32-bit float | Float4 | f32 | f32.MyFloatVariable |
| MyFloatVariable__f32 | |
32-bit integer as a SCADA Boolean | Boolean | i32b | i32b.MyIntVariable |
| MyIntVariable__i32b | |
String | String | s | s.MyStringVariable | PAC Controllers support only 7-bit ASCII | MyStringVariable__s | |
Up or Down timer | Float4 | t | t.MyUpTimer | t.MyUpTimer | Only read-only | MyUpTimer__t |
32-bit integer table element as a SCADA int4 | Int4 | i32te | i32te.My32BitIntegerTable[3] | i32te.My32BitIntegerTable[3].rw |
| My32BitIntegerTable__3_i32te |
32-bit integer table | See i32te. | i32t | i32t.My32BitIntegerTable[0-9] | i32t.My32BitIntegerTable[0-9].rw | Module will provide individual elements. |
...
tag’s item ID. i32tMyInteger[11-9] (backward index range) | My32BitIntegerTable__0_9_i32t | |||||
64-bit integer table element as a SCADA int8 | Int8 | i64te | i64te.My64BitIntegerTable[302] | i64te.My64BitIntegerTable[302].rw |
| My64BitIntegerTable__302_i64te |
64-bit integer table | See i64te. | i64t | i64t.My64BitIntegerTable[0-35] | i64t.My64BitIntegerTable[0-35].rw | Module will provide individual elements. "_auto" will be appended to the |
...
tag’s item ID. | My64BitIntegerTable__0_35_i64t | |||||
32-bit float table element as a SCADA float4 | Float4 | f32te | f32te.My32BitFloatTable[11] | f32te.My32BitFloatTable[11].rw |
| My32BitFloatTable__11_f32te |
32-bit float table | See f32te. | f32t | f32.MyFloatTable[0-20] | f32.MyFloatTable[0-20].rw | Module will provide individual elements. "_auto" will be appended to the |
...
tag’s item ID. | MyFloatTable__0_20_f32 | ||||
String table | See stte. | st | st.MyStringTable[0-32] | st.MyStringTable[0-32].rw | PAC Controllers support only 7-bit ASCII Module will provide individual elements. |
...
tag’s item ID. | MyStringTable__0_32_st | |||||
String table element as a SCADA string | String | stte | stte.MyStringTable[6] | stte.MyStringTable[6].rw | PAC Controllers support only 7-bit ASCII | MyStringTable__6_stte |
Analog input or output state | Float4 | aio | aio.MyAnalogPoint |
| MyAnalogPoint__aio | |
Discrete input or output state | Boolean | dio | dio.MyDiscretePoint |
| MyDiscretePoint__dio | |
Bit-pick of a 32-bit integer variable | Boolean | i32bp | i32bp.My32BitIntegerVariable.31 |
| My32BitIntegerVariable__31_i32bp | |
Bit-pick of a 64-bit integer variable | Boolean | i64bp | i64bp.MyLongVariable.0 |
| MyLongVariable__0_i64bp | |
Bit-pick of a 32-bit integer table element | Boolean | i32tebp | i32tebp.My32BitIntegerTable[3].2 | i32tebp.My32BitIntegerTable[3].2.rw |
| My32BitIntegerTable__3_2_i32tebp |
Bit-pick of a 64-bit integer table element | Boolean | i64tebp | i64tebp.My64BitIntegerTable[302].6 | i64tebp.My64BitIntegerTable[302].6.rw |
| My64BitIntegerTable__302_6_i64tebp |
...
...
...
...
...
...
...
...
...
...
...
...
...
Anchor | ||||
---|---|---|---|---|
|
...