In MQTT Transmission and MQTT Engine support was added to transmit alarm events from the Edge to the Central Gateway. They also now support acknowledgements from the Central Gateway back to the Edge.
...
Add a line similar to the following to the data/ignition.conf file but replace the 'XX' with the proper index per the wrapper.java.additional statements. This must be done on both the MQTT Transmission side as well as the MQTT Engine side.
Code Block |
---|
wrapper.java.additional.XX=--add-opens=java.base/java.util.concurrent.atomic=ALL-UNNAMED |
At this point, we can Acknowledge the alarm via the Alarm Status Table by clicking the 'Acknowledge' button as shown below:
Info |
---|
The alarm can be acknowledged on either the Edge or the Central Gateway side. Once ackowledged, it will be reflected as so on both the Edge and the Central Gateway sides |
In MQTT Transmission and MQTT Engine v4.0.16 support was added to propagate triggered alarm events from the Edge to a Central Ignition Gateway. This can be used to insert alarm events into Ignition's alarm journal on the MQTT Engine side. Currently, these alarm events on the MQTT Engine side can not be currently be used in alarm pipelines, and they can not be remotely acknowledged from MQTT Engine back to MQTT Transmission.
...