Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

  • Type
    • The type of History Store with options of In-Memory and Disk-Backed (available in 4.0.17)
    • Data stored in an In-Memory History Store will not be persisted across a module configuration change, module disable/enable, module restart or power loss. 
    • Data stored in a Disk-Backed History Store will persist across a module configuration change, module disable/enable, module restart or power loss.
  • Message Capacity - deprecated in 4.0.19
    • The maximum number of messages to store before dropping the oldest historical messages
  • History Max Size
    • The maximum number of megabytes history can use before dropping the data
    • In_Memory Store & Forward will use the Ignition Java Heap memory
    • Default is 500
  • History Max Age
    • Maximum number of minutes to store history before dropping the data.
    • Default 44640 (31 days)
  • Flush Period
    • The period to wait in milliseconds between publishes when flushing messages upon reestablishing communication.
    • The publishing of historic data messages is interleaved with the publishing of live data messages. 
    • Default 100

...