  • Ignition Primary - MQTT Distributor
    • No modifications to the default parameters are required.  However, it is important to make sure the Operation System allows inbound connections on port 1883 and there are no firewalls blocking inbound connections on this port from the remote edge nodes.
  • Ignition Primary - MQTT Engine
    • The only change from defaults is to set a Primary Host ID.  MQTT uses Quality of Service (QOS) levels to ensure messages get delivered.  However, this only ensures delivery between a single MQTT client and the MQTT server.  In other words, it doesn't ensure delivery from one MQTT client to another MQTT client.  Sparkplug introduces the notion of a Primary Host ID which is used to ensure client to client communications.  The only requirement is that it match exactly on both the MQTT Engine and MQTT Transmission configurations.
  • Ignition Edge 1 and Ignition Edge 2 - MQTT Transmission (Configure the same on both Ignition instances)
    • As with the MQTT Engine configuration, the Primary Host ID must be set on the General tab as shown below.
    • Delete the existing default MQTT Transmission Server.
      Image Modified

    • Create a new MQTT Server configuration by clicking the link below.

      image2017-9-5_13-45-36.png
    • Configure MQTT Transmission to point to the Primary Ignition.  Configure as shown below making sure to change the URL to reflect your network settings.  For example, if you Ignition Primary is at 192.168.1.100 the MQTT Server URL would be: tcp://192.168.1.100:1883.  After setting the parameters as shown below.  Click the 'Save Changes' button at the bottom.
      Image Modified
    • Verify the MQTT Server has been created and is shown in the list of MQTT Servers as shown below.

    • Repeat the process of creating a MQTT Server but instead point it to the Ignition Primary Backup MQTT Server.  These are the parameters to use:
      • Name: primary-backup
      • URL: tcp://primary-backup:1883
        • Change 'primary-backup' in the URL to reflect the network address of the Ignition Primary Backup server.
      • Server Type: MQTT Distributor
      • Server Set: Default
      • Username: admin
      • Password: changeme
    • When complete, verify both MQTT Servers appear in the list as shown below.
    • Finally, make sure to set up the same MQTT Transmission configuration in the Ignition Edge 2 instance.

...

  • Ignition Primary
    • Select Redundancy on the left navigation bar. Then set the Mode to 'Master' and set the Standby Activity left to 'Warm' as shown below.
      Image Modified
    • Set up the Redundancy Network Settings.  The settings here are specific to your network setup.  On many LAN configurations none of these changes are required.  What is shown below was the configuration for setting up all of these components in Amazon's AWS EC2 instances.  The changes were:
      • Uncheck 'Auto-detect network interface'
      • Set the 'Network Bind Interface' to the public IP address of the Ignition Primary EC2 instance.  On a LAN this would be the primary network interface address of the Ignition Primary machine.
      • Uncheck the 'Autodetect HTTP Address' tickbox.
      • Specify two explicit HTTP addresses for clients to use.  These were the public IP addresses of the Ignition Primary and Ignition Primary Backup EC2 instances.  On a LAN, these would be the primary network interface addresses of the Ignition Primary and Ignition Primary Backup machines.  Also note the HTTP port is 8088 which is the default Ignition HTTP port.
    • Set the Master Node Address.  Note in the configuration below a hostname is being used.  This should be the primary network interface address of the Ignition Primary Gateway.
    • Finally, click the 'Save Changes' button.
  • Ignition Primary Backup
    • Select Redundancy on the left navigation bar. Then set the Mode to 'Backup' and set the Standby Activity left to 'Warm' as shown below.
    • Set up the Redundancy Network Settings.  The settings here are specific to your network setup.  On many LAN configurations none of these changes are required.  What is shown below was the configuration for setting up all of these components in Amazon's AWS EC2 instances.  The changes were:
      • Uncheck 'Auto-detect network interface'
      • Set the 'Network Bind Interface' to the public IP address of the Ignition Primary Backup EC2 instance.  On a LAN this would be the primary network interface address of the Ignition Primary Backup machine.
      • Uncheck the 'Autodetect HTTP Address' tickbox.
      • Specify two explicit HTTP addresses for clients to use.  These were the public IP addresses of the Ignition Primary and Ignition Primary Backup EC2 instances.  On a LAN, these would be the primary network interface addresses of the Ignition Primary and Ignition Primary Backup machines.  Also note the HTTP port is 8088 which is the default Ignition HTTP port.Image Modified
    • Set the Master Node Address.  Note in the configuration below a hostname is being used.  This should be the primary network interface address of the Ignition Primary Gateway.
      Image Modified
    • Finally, click the 'Save Changes' button.

  • Ignition Edge 1
    • Select Redundancy on the left navigation bar. Then set the Mode to 'Master' and set the Standby Activity left to 'Warm' as shown below.
      Image Modified
    • Set up the Redundancy Network Settings.  The settings here are specific to your network setup.  On many LAN configurations none of these changes are required.  What is shown below was the configuration for setting up all of these components in Amazon's AWS EC2 instances.  The changes were:
      • Uncheck 'Auto-detect network interface'
      • Set the 'Network Bind Interface' to the public IP address of the Ignition Edge 1 EC2 instance.  On a LAN this would be the primary network interface address of the Ignition Edge 1 machine.
      • Uncheck the 'Autodetect HTTP Address' tickbox.
      • Specify two explicit HTTP addresses for clients to use.  These were the public IP addresses of the Ignition Edge 1 and Ignition Edge 1 Backup EC2 instances.  On a LAN, these would be the primary network interface addresses of the Ignition Edge 1 and Ignition Edge 1 Backup machines.  Also note the HTTP port is 8088 which is the default Ignition HTTP port.Image Modified
    • Set the Master Node Address.  Note in the configuration below a hostname is being used.  This should be the primary network interface address of the Ignition Edge 1 Gateway.
      Image Modified
    • Finally, click the 'Save Changes' button.

  • Ignition Edge 1 Backup
    • Select Redundancy on the left navigation bar. Then set the Mode to 'Backup' and set the Standby Activity left to 'Warm' as shown below.
      Image Modified
    • Set up the Redundancy Network Settings.  The settings here are specific to your network setup.  On many LAN configurations none of these changes are required.  What is shown below was the configuration for setting up all of these components in Amazon's AWS EC2 instances.  The changes were:
      • Uncheck 'Auto-detect network interface'
      • Set the 'Network Bind Interface' to the public IP address of the Ignition Edge 1 Backup EC2 instance.  On a LAN this would be the primary network interface address of the Ignition Edge 1 Backup machine.
      • Uncheck the 'Autodetect HTTP Address' tickbox.
      • Specify two explicit HTTP addresses for clients to use.  These were the public IP addresses of the Ignition Edge 1 and Ignition Edge 1 Backup EC2 instances.  On a LAN, these would be the primary network interface addresses of the Ignition Edge 1 and Ignition Edge 1 Backup machines.  Also note the HTTP port is 8088 which is the default Ignition HTTP port.Image Modified
    • Set the Master Node Address.  Note in the configuration below a hostname is being used.  This should be the primary network interface address of the Ignition Edge 1 Gateway.
      Image Modified
    • Finally, click the 'Save Changes' button.
  • Ignition Edge 2
    • Select Redundancy on the left navigation bar. Then set the Mode to 'Master' and set the Standby Activity left to 'Warm' as shown below.
      Image Modified
    • Set up the Redundancy Network Settings.  The settings here are specific to your network setup.  On many LAN configurations none of these changes are required.  What is shown below was the configuration for setting up all of these components in Amazon's AWS EC2 instances.  The changes were:
      • Uncheck 'Auto-detect network interface'
      • Set the 'Network Bind Interface' to the public IP address of the Ignition Edge 2 EC2 instance.  On a LAN this would be the primary network interface address of the Ignition Edge 2 machine.
      • Uncheck the 'Autodetect HTTP Address' tickbox.
      • Specify two explicit HTTP addresses for clients to use.  These were the public IP addresses of the Ignition Edge 2 and Ignition Edge 2 Backup EC2 instances.  On a LAN, these would be the primary network interface addresses of the Ignition Edge 2 and Ignition Edge 2 Backup machines.  Also note the HTTP port is 8088 which is the default Ignition HTTP port.Image Modified
    • Set the Master Node Address.  Note in the configuration below a hostname is being used.  This should be the primary network interface address of the Ignition Edge 2 Gateway.
      Image Modified
    • Finally, click the 'Save Changes' button.

  • Ignition Edge 2 Backup
    • Select Redundancy on the left navigation bar. Then set the Mode to 'Backup' and set the Standby Activity left to 'Warm' as shown below.
      Image Modified
    • Set up the Redundancy Network Settings.  The settings here are specific to your network setup.  On many LAN configurations none of these changes are required.  What is shown below was the configuration for setting up all of these components in Amazon's AWS EC2 instances.  The changes were:
      • Uncheck 'Auto-detect network interface'
      • Set the 'Network Bind Interface' to the public IP address of the Ignition Edge 2 Backup EC2 instance.  On a LAN this would be the primary network interface address of the Ignition Edge 2 Backup machine.
      • Uncheck the 'Autodetect HTTP Address' tickbox.
      • Specify two explicit HTTP addresses for clients to use.  These were the public IP addresses of the Ignition Edge 2 and Ignition Edge 2 Backup EC2 instances.  On a LAN, these would be the primary network interface addresses of the Ignition Edge 2 and Ignition Edge 2 Backup machines.  Also note the HTTP port is 8088 which is the default Ignition HTTP port.Image Modified
    • Set the Master Node Address.  Note in the configuration below a hostname is being used.  This should be the primary network interface address of the Ignition Edge 2 Gateway.
      Image Modified
    • Finally, click the 'Save Changes' button.

...

  • Using Ignition Designer on Edge 1, do the following:
    • Create a new project called 'Test'.
    • In the Tag Browser, confirm there is a folder called 'Edge Nodes'.  If there is not, confirm MQTT Transmission is installed.
    • In the 'Edge Nodes' folder, create a folder called 'Group 1'.
    • In the 'Group 1' folder, create a folder called 'Edge 1'.
    • In the 'Edge 1' folder, create a folder called 'Device 1'.
    • In the 'Device 1' folder, create a Tag called 'Tag 1'.
    • At the end, you should see something similar to what is shown below.

Image Modified

  • Using Ignition Designer on Edge 2, do the following:
    • Create a new project called 'Test'.
    • In the Tag Browser, confirm there is a folder called 'Edge Nodes'.  If there is not, confirm MQTT Transmission is installed.
    • In the 'Edge Nodes' folder, create a folder called 'Group 1'.
    • In the 'Group 1' folder, create a folder called 'Edge 2'.
    • In the 'Edge 2' folder, create a folder called 'Device 1'.
    • In the 'Device 1' folder, create a Tag called 'Tag 1'.
    • At the end, you should see something similar to what is shown below

Image Modified 

  • Finally, refresh the Transmission runtime.  This is done by clicking the 'MQTT Transmission/Transmission Control/Refresh' Boolean tag.

Image Modified

    • After clicking the Boolean tag you may need to 'Enable Read/Write Mode'

...

  • Repeat the following steps for the following Ignition instances: Primary, Edge 1, and Edge 2
    • Browse to the Status menu and then click in the Redundancy box as shown below.

      Image Modified 
      • Force the Re-sync via the button below.  This will duplicate the master configuration to the backup Ignition instance it is connected to.
        Image Modified
      • Repeat the above Re-sync steps on the Edge 1 and Edge 2 Ignition instances.

...

Open Ignition Designer on the Ignition Primary instance.  Expand the MQTT Engine tag tree and validate the following tags are present.  If they are present and not stale, they are properly connected.

Image Modified

Step 8: Test the Redundancy

...

  • At this point we can begin failing Ignition instances.  From the Status → Redundancy page we can use the 'Force Failover' button as shown below.  Of course stopping the actual Ignition instance is another option.

Image Modified

  • Primary Ignition Failure: Failing the Ignition Primary instance will cause the following.
    • Ignition Primary will go down and be unreachable
      • This results in all MQTT connections being lost.
    • Ignition Primary Backup will come up and take the place of Ignition Primary
    • MQTT Engine will reconnect on Ignition Primary
    • The MQTT Transmission instances will reconnect to the new MQTT Server (MQTT Distributor) running in Ignition Primary Backup
    • This is all shown in the screenshot below of the Ignition projects.  Note all connections are valid and the 'Redundancy Role' of Ignition Primary is now Backup.

...