Below is a table of decoded Ignition 8 Quality codes (Python script below that was used to generate this list on Ignition 8.1.13)
Quality | Code | Ignition Subcode |
---|---|---|
Good_Unspecified | 0 | 0 |
Good_WritePending | 2 | 2 |
Good | 192 | 192 |
Good_Provisional | 200 | 200 |
Good_Initial | 201 | 201 |
Good_Overload | 202 | 202 |
Good_Backfill | 203 | 203 |
Uncertain | 1073742080 | 256 |
Uncertain_LastKnownValue | 1073742081 | 257 |
Uncertain_InitialValue | 1073742082 | 258 |
Uncertain_DataSubNormal | 1073742083 | 259 |
Uncertain_EngineeringUnitsExceeded | 1073742084 | 260 |
Uncertain_IncompleteOperation | 1073742085 | 261 |
Bad | -2147483136 | 512 |
Bad_Unauthorized | -2147483135 | 513 |
Bad_AccessDenied | -2147483134 | 514 |
Bad_Disabled | -2147483133 | 515 |
Bad_Stale | -2147483132 | 516 |
Bad_TrialExpired | -2147483131 | 517 |
Bad_LicenseExceeded | -2147483130 | 518 |
Bad_NotFound | -2147483129 | 519 |
Bad_ReferenceNotFound | -2147483128 | 520 |
Bad_AggregateNotFound | -2147483127 | 521 |
Bad_NotConnected | -2147483126 | 522 |
Bad_GatewayCommOff | -2147483125 | 523 |
Bad_OutOfRange | -2147483124 | 524 |
Bad_DatabaseNotConnected | -2147483123 | 525 |
Bad_ReadOnly | -2147483122 | 526 |
Bad_Failure | -2147483121 | 527 |
Bad_Unsupported | -2147483120 | 528 |
Error | -1073741056 | 768 |
Error_Configuration | -1073741055 | 769 |
Error_ExpressionEval | -1073741054 | 770 |
Error_TagExecution | -1073741053 | 771 |
Error_TypeConversion | -1073741052 | 772 |
Error_DatabaseQuery | -1073741051 | 773 |
Error_IO | -1073741050 | 774 |
Error_TimeoutExpired | -1073741049 | 775 |
Error_Exception | -1073741048 | 776 |
Error_InvalidPathSyntax | -1073741047 | 777 |
Error_Formatting | -1073741046 | 778 |
Error_ScriptEval | -1073741045 | 779 |
Error_CycleDetected | -1073741044 | 780 |
...