Creating alarms on Ignition tags being consumed by MQTT Transmission on the Edge Gateway requires no special configuration; simply create the alarm on the desired tag as documented here.
A common scenario beyond simply creating the alarm is propagating the alarm configuration of a tag to the Central Gateway so it can be managed on the Edge, but present at both the Edge and Central Gateway.
...
Note |
---|
The recommended best practice for alarm propagation from the Edge to the Central Gateway is to use the Ignition Gateway Network to propagate alarms between gateways. |
In MQTT Transmission and MQTT Engine v4.0.16 support was added to propagate triggered alarm events from the Edge to a Central Ignition Gateway. This can be used to insert alarm events into Ignition's alarm journal on the MQTT Engine side. Currently, these alarm events on the MQTT Engine side can not be currently be used in alarm pipelines and they can not be remotely acknowledged from MQTT Engine back to MQTT Transmission.
To configure alarm event propagation from Transmission to Engine to insert them into the Engine side alarm journal, follow these steps.
Add a line similar to the following to the data/ignition.conf file but replace the 'XX' with the proper index per the wrapper.java.additional statements. This must be done on both the MQTT Transmission side as well as the MQTT Engine side.
Code Block |
---|
wrapper.java.additional.XX=--add-opens=java.base/java.util.concurrent.atomic=ALL-UNNAMED |
Excerpt Include | ||||||
---|---|---|---|---|---|---|
|