| Quality | Code | Subcode |
|---|---|---|
| Good_Unspecified | 0 | 0 |
| Good_WritePending | 2 | 2 |
| Good | 192 | 192 |
| Good_Provisional | 200 | 200 |
| Good_Initial | 201 | 201 |
| Good_Overload | 202 | 202 |
| Good_Backfill | 203 | 203 |
| Uncertain | 1073742080 | 256 |
| Uncertain_LastKnownValue | 1073742081 | 257 |
| Uncertain_InitialValue | 1073742082 | 258 |
| Uncertain_DataSubNormal | 1073742083 | 259 |
| Uncertain_EngineeringUnitsExceeded | 1073742084 | 260 |
| Uncertain_IncompleteOperation | 1073742085 | 261 |
| Bad | -2147483136 | 512 |
| Bad_Unauthorized | -2147483135 | 513 |
| Bad_AccessDenied | -2147483134 | 514 |
| Bad_Disabled | -2147483133 | 515 |
| Bad_Stale | -2147483132 | 516 |
| Bad_TrialExpired | -2147483131 | 517 |
| Bad_LicenseExceeded | -2147483130 | 518 |
| Bad_NotFound | -2147483129 | 519 |
| Bad_ReferenceNotFound | -2147483128 | 520 |
| Bad_AggregateNotFound | -2147483127 | 521 |
| Bad_NotConnected | -2147483126 | 522 |
| Bad_GatewayCommOff | -2147483125 | 523 |
| Bad_OutOfRange | -2147483124 | 524 |
| Bad_DatabaseNotConnected | -2147483123 | 525 |
| Bad_ReadOnly | -2147483122 | 526 |
| Bad_Failure | -2147483121 | 527 |
| Bad_Unsupported | -2147483120 | 528 |
| Error | -1073741056 | 768 |
| Error_Configuration | -1073741055 | 769 |
| Error_ExpressionEval | -1073741054 | 770 |
| Error_TagExecution | -1073741053 | 771 |
| Error_TypeConversion | -1073741052 | 772 |
| Error_DatabaseQuery | -1073741051 | 773 |
| Error_IO | -1073741050 | 774 |
| Error_TimeoutExpired | -1073741049 | 775 |
| Error_Exception | -1073741048 | 776 |
| Error_InvalidPathSyntax | -1073741047 | 777 |
| Error_Formatting | -1073741046 | 778 |
| Error_ScriptEval | -1073741045 | 779 |
| Error_CycleDetected | -1073741044 | 780 |
| Warning |
|---|
| Cirrus Link provides these scripts as examples only, they are not supported or guaranteed to meet any particular functionality. Cirrus Link cannot provide any assistance to modify these scripts to meet a particular need. |
| Code Block | ||
|---|---|---|
| ||
# Cirrus Link provides these scripts as examples only, they are not supported or guaranteed to meet any particular functionality. Cirrus Link cannot provide any assistance to modify these scripts to meet a particular need.
from com.inductiveautomation.ignition.common.model.values import QualityCode
codesAsJson = QualityCode.getCodesJson()
print codesAsJson
for code in codesAsJson:
print "%s, %s, %s" % (codesAsJson[code], code, int(code) & 0xFFFF) |
...